DESIGN OF LOW VOLTAGE LIGHTING SYSTEM
DESIGN OVERVIEW:
LVL system is a creative and flexible alternative for
low voltage lighting. It is easy to
install, safe to operate and maintain longer lamp life and significant energy
savings. The two components of LVL system are
class 2 cable and
transformer.
12 VOLT TRANSFORMER SIZING:
Transformer reduces 120V to a safe 12V needed for low voltage lamps. The total
lamp wattage of all fixtures connected to a transformer must be less than the
capacity of transformer. To determine the size, add up wattage of all lamps and
add 10% more for safety factor.
TRANSFORMER SIZE = TOTAL FIXTURES WATT X 1.1
Select a transformer that matches as close as to your total lamp wattage. If total wattage is too great, either divide the load between two transformers or use a more powerful model.
LOW VOLTAGE CABLE LENGTH:
Voltage drop has an important impact on LVL systems. Voltage drop occurs along
the length of cable and lamps at the end of run dimmer at the beginning. Voltage
drop is a function of cable length, cable size, and total fixtures wattage.
Voltage drop can be minimized in several different ways:
LOW VOLTAGE CABLE LENGTH GUIDE
MAXIMUM CABLE LENGTH PER TOTAL FIXTURE WATTS |
|||||||
Cable Size | Cable Constant | 50W | 100W | 150W | 200W | 250W | 300W |
12-2 | 7500 | 300' | 150' | 100' | 75' | 60' | ----- |
CABLE LENGTH FORMULA:
MAX. CABLE LENGTH: | CABLE SIZE CONSTANT | x 2 |
------------------------------------ | ||
TOTAL FIXTURES WATTS |
TIP: | Expect a voltage drop of greater than 2 volts when cable length is longer than recommended. |
Use the above chart of formula to calculate max. cable length. |
12 VOLT CABLE LAYOUT OPTIONS
TIP: Connect all lamps in parallel. Connect one side to "COM" and other side to "12V" terminal.
LOOP INSTALLATION: Fixtures are arranged in a loop, reducing voltage drop. |
|
SPLIT LOAD INSTALLATION: Fixtures run is two or more directions from transformer. Locating the transformer in the center of run reduces the effect of voltage drop. |
|
STRAIGHT RUN INSTALLATION: Fixtures run in sequence directly from transformer |
|
"T" INSTALLATION: Allows more equal distribution of power to center of the run, or to run some distance away. Main cable must be heavier gauge (10-2 or 8-2). |
|
TROUBLE SHOOTING CHECKLIST |
|
ENTIRE SYSTEM WILL NOT OPERATE
|
CIRCUIT BREAKER ON TRANSFORMER TRIPS
|
FIXTURES ON, BUT DIMS
|
|
CIRCUIT BREAKER ON TRANSFORMER TRIPS
|
FIXTURE WILL NOT LIGHT
|